Gaseous Generator Models
Model PSS21 PSS30 PSS40 PSS60 PSS90 GR110 GR150 GR180
Manufacturer
WINCO PACKAGED STANDBY SYSTEM
WINPOWER GR
Engine Data
Engine Make GM GM GM GM GM GM GM Doosan
Engine Model 3.0L 3.0L 4.3L 5.7L 5.7L TAC 8.1L T 8.1L TAC 11.05L TAC
Cylinders In-line 4 In-line 4 V-6 V-8 V-8 V-8 V-8 In-line 6
Speed 1800 rpm 1800 rpm 1800 rpm 1800 rpm 1800 rpm 1800 rpm 1800 rpm 1800 rpm
Fuel Consumption
100% Load LP 3.9 gal/hr 4.83 gal/hr 5.91 gal/hr 9.29 gal/hr 12.4 gal/hr 582 ft
3
/hr 703 ft
3
/hr
100% Load NG 240 ft
3
/hr 432 ft
3
/hr 499 ft
3
/hr 799 ft
3
/hr 1149 ft
3
/hr 1651 ft
3
/hr 1752 ft
3
/hr 2115 ft
3
/hr
Electrical Performance (LP/NG)(1)
120/240 1-PH (Amps) 88/88 125/125 167/167 233/229 333/375 458/458 500/583 533/712
120/208 3-PH (Amps) 76/76 104/104 139/139 208/201 278/312 382/382 433/521 469/625
120/240 3-PH (Amps) 66/66 90/90 120/120 180/174 240/270 331/331 375/452 406/542
277/480 3-PH (Amps) 37/37 45/45 60/60 90/87 120/135 166/166 187/226 203/271
Max Standby Rating (2)(3) 25 kW 30 kW 40 kW 60 kW 90 kW 110 kW 150 kW 180 kW
General Information
Control Panel DSE 7110 DSE 7310
Warranty (4) Engine: 3 Years/3500 Hours Generator: 1 Year/1000 Hours
Notes: (1) All electrical ratings assume 1.0 pf for single phase and 0.8 pf for three phase. All ratings are standby. (2) Highest rating at optimal voltage and power factor. (3)Derate 10% for
prime power. All models except GR180 require on-site emissions certications for prime power. (4) Engine limited warranty administered through engine manufacturer. Warranty applies to
GM engines only. Contact factory for full warranty information.
Automatic Standby Generators
Diesel Generator Models
Model DR12K2 DR20I4 DR30I4 DR45I4 DR65I4 DR90I4 DR100I4 DR130I4 DR175I4 DR200D4 DR250I4 DR300I4 DR350I4
Winpower DR
Engine Data
Make Kohler Isuzu Isuzu Iveco Iveco Iveco Iveco Iveco Iveco Deutz Iveco Iveco Iveco
Model
KDW1003 4LE1 4LE1T N45SM1 N45SM2 N45TM2 N67TM1 N67TM1 N67TE2
BF6M1013FC
C87TE1D C10TE1D C13TE3X
Cylinders In-line 3 In-Line 4 In-line 4 In-Line 4 In-Line 4 In-line 4 In-line 6 In-line 6 In-line 6 In-line 6 In-line 6 In-line 6 In-line 6
Displacement 1028 cc 2.2L 2.2L 4.5L 4.5L 4.5L 6.7L 6.7L 6.7L 7.1L 8.7L 10.3L 13L
Speed (rpm) 3600 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800
Fuel Consumption (gal/hr)
100% Load 1.27 1.80 1.99 4.09 4.57 6.94 8.10 8.80 12.42 13.00 16.98 20.20 24.50
50% Load 0.79 0.90 1.00 2.16 2.38 3.57 4.10 5.31 6.45 7.00 10.25 11.50 14.35
Electrical Performance (Amps)(1)(2)(3)
120/240 1-PH 50 83 125 187 258 358 416 512 695 833 NA NA NA
120/208 3-PH 42 69 104 156 215 312 364 451 608 695 867 1041 1111
120/240 3-PH 36 60 90 135 186 271 315 391 527 602 752 902 960
277/480 3-PH 18 30 45 68 93 135 172 195 263 301 376 451 526
Max Standby 12 kW 20 kW 30 kW 45 kW 62 kW 90 kW 115 kW 130 kW 175 kW 200 kW 250 kW 300 kW 350 kW
General Information
Control Panel DSE7110 DSE7310
Warranty (4) Engine: 5 Years/2000 Hours Generator: 1 Year/1000 Hours
Notes: (1) All electrical ratings assume 1.0 pf for single phase and 0.8 pf for three phase. All ratings are standby. (2) Max standby rating is at optimal voltage and power factor. (3) Derate
10% for prime power. (4) Engine limited warranty administered through engine manufacturer. Deutz warranty covers 2 years/3000 hours. Contact factory for full warranty information.
WINCO and WINPOWER liquid-cooled automatic standby
generators are designed to reliably deliver power when
you need it, even when you are not on site. Each generator
is designed to automatically provide back-up power for
industrial applications making them suitable for anything
from home standby to critical care facilities. To protect
your investment, a sophisticated digital controller starts,
monitors and shuts down your generator. If any key operating
parameters are out of tolerance, the generator will provide a
warning or immediately shut-down if the problem is serious
enough. WINCO and WINPOWER offer the best features for
the best long-term value.
Standard Features
WINCO and WINPOWER build each standby generator with the necessary
features to provide reliable back-up power. We don’t offer introductory units
that lack essential features.
Premium Deep Sea 7110 and 7310 genset controllers.•
Kim Hotstart jacket heater included standard.•
Standard 3-stage battery charger increases battery life.•
Premium Square D mainline circuit breakers.•
Battery rack and cables included standard (Battery not included).•
Each unit is 100% load tested. •
10