IRRIGATION 120/240V 1-PH 120/208V 3-PH SHAFT
WEIGHT
MODEL WATTS DBL DELTA 120/240V 3-PH 277/480 3-PH INPUT RPM DIAMETER
PI044H2 8.5 kW 13.9 kW 16.6 kW 17.7 kW 1800 rpm 42 mm 261 lbs
PI144D2 10.0 kW 14.3 kW 19.0 kW 21.0 kW 1800 rpm 42 mm 291 lbs
PI144E2 12.5 kW 17.8 kW 23.7 kW 25.2 kW 1800 rpm 42 mm 323 lbs
PI144F2 15.0 kW 19.7 kW 26.1 kW 27.8 kW 1800 rpm 42 mm 332 lbs
PI144G2 17.5 kW 21.4 kW 28.4 kW 31.5 kW 1800 rpm 42 mm 368 lbs
PI144J2 20.0 kW 28.5 kW 38.7 kW 39.9 kW 1800 rpm 42 mm 441 lbs
PI144K2 25.0 kW 36.2 kW 42.5 kW 46.2 kW 1800 rpm 42 mm 461 lbs
Notes: (1) Motor starting based upon 1 kW = 1 HP motor starting for 480V 3-PH (2) All models include the EBS standard (3) All models
are 12-Lead reconnectable (4) Most units drop ship from Stamford. Contact factory for availability.
Stamford 2-Bearing Generator
Irrigation and Industrial Applications
MODEL 2FSM2PC-1 8KS2GC-3 (1) TB2400C TB4000C (2) TB6000C (2) TB7200GFI (2)
Watts 2000 (3) 8000 2400 4000 (3) 6000 7200
Amps 16.7 66.6/33.3 20 33.3/16.6 50/25 60/30
Volts (60 HZ) 120 120/240 120 120/240 120/240 120/240
Rotor Speed 3600 rpm 3600 rpm 3600 rpm 3600 rpm 3600 rpm 3600 rpm
Motor Starting .5 hp 3 hp .75 hp 1.5 hp 3 hp 5 hp
Generator Type Brush Brush Brushless Brushless Brushless Brushless
Receptacles
120V NEMA 5-15R 2 2 - - - -
120V NEMA 5-20R - - 2 4 4 -
120V NEMA L5-15R - - - - - 4
240V NEMA 6-15R - 2 - - - -
240V NEMA 6-50R - 1 - - - -
120/240V NEMA L14-30R - - - 1 1 1
Circuit Breakers UL Only - Included Included Included Included
Length 15” 19” 14.25” 17.75” 17.75” 15.13”
Width 6.5” 12” 8.5” 8.5” 8.5” 8.5”
Height 6.75” 17.75” 8.94” 8.94” 8.94” 8.94”
Shaft Diameter .625” 1.25” 1.125” 1.125” 1.125” 1.125”
Weight 56 lbs 175 lbs 61 lbs 67 lbs 86 lbs 67 lbs
Warranty (4) 1 yr 1 yr 1 yr 1 yr 1 yr 1 yr
Notes: (1) AC voltmeter included standard (2) Unit can be reconnected for 120 volt full power (3) Available in a UL version. Specify UL
when ordering.
Two-Bearing Generators
1800 RPM Operation•
Keyed Shaft•
+/-1% Voltage Regulation•
Electronic Automatic Voltage Regulator (AVR)•
Excitation Boost System (EBS) Standard Withstands •
300% Short Circuit
12LeadReconnectable(Shipsin480VConguration)•
Clean Power, <5% Total Harmonic Distortion•
FeaturesandBenets
There is no question that WINCO’s two-bearing generators are the most rugged generators on the market. Epoxy baked rotors,
oversized diodes, cast iron drive-side end brackets, and double sealed permanent bearings all combine to ensure maximum
performanceandlife.Unitsaredesignedtorotateineitherdirectionwithoutrewiringmakingthemveryexibleforanyapplication.
Each generator is rated at unity power factor, requiring approximately two horse power of input for each 1,000 watts of output from
the generator. Each unit is 100% factory tested instead of statistical sampling to ensure performance and reliability.