Digital Controller Features
Engine Display/Protection DSE 7110 DSE 7310
Engine RPM X X
Low Oil Pressure X X
High Coolant Temp X X
Low Coolant Level Optional Optional
Overspeed X X
Underspeed X X
Overcrank X X
Charging Alternator Fail X X
CAN ECU Shutdown X X
Genset Display/Protection
Voltage (L-N) Display X X
Voltage (L-L) Display X X
Overvoltage Shutdown X X
Undervoltage Shutdown X X
Frequency Display X X
Overfrequency Shutdown X X
Underfrequency Shutdown X X
Phase Imbalance - Disabled
Amp Display/Shutdown X X
kW, kVAh, kVArh Display - X
kWh, kVAh, kVArh Display - X
Generator Phase Sequence - X
Earth Current - Optional
Additional Displays/Protections
Emergency Stop X X
Fuel Leak/Sender Failure X X
High Fuel Level Optional Optional
Low Fuel Level X X
Fuel Level Gauge (Digital) X X
Battery Voltage X X
Battery Over/Under Voltage X X
Battery Charger Failure Optional Optional
Communications
USB Connectable X X
RS232/RS485 X X
NFPA Annunciator - X
Remote Display Panel - 3xDSE2510
Ethernet - Optional
Additional Features
Audible Alarm - X
Engine Exerciser Programmable
Maintenance Interval Timer 1 Event 3 Events
Load Shedding/Dummy - 5 Step
Congurable Inputs 7 9-24w/DSE2130
Congurable Outputs 8 6-80w/DSE2751
Event Log 5 250
Alternative Congurations 1 3
UL/CSA Listed X X
NFPA 110 Level 1
Critical care facilities
like nursing homes and
hospitals require upgraded
components like larger
battery chargers, jacket
heaters, and remote
annunciators. Each
generator can be ordered in
a conguration that meets
NFPA 110 Level 1 standards
(requires DSE 7310).
Sub-Base Diesel Fuel Tanks
Each WINPOWER diesel generator is compatible with UL 142 sub-base fuel tanks.
Constructed of heavy duty steel with a 110% secondary containment system
prevents costly environmental disasters. Other standard features include leak
detection, digital and mechanical fuel gauges, UL approved vents, bafes and
lockable fuel caps. The DR12K2 and DR20I4 are available with 32 gallon composite
tanks that are secured in the base. Composite tanks are not UL142 approved.
Housing Options
All housings are constructed of 16 gauge (Winco) 14 gauge (Winpower) galvaneel
steel with DuPont powder coat paint to protect against corrosion. Each housing
comes with identically keyed lockable doors, drip edges, critical grade exhaust and
sound absorbing foam. Each generator is designed to be rodent proof.
WINCO PSS: Each unit comes standard
with a sound attenuated housing.
WINPOWER Powr-Pak: Each
WINPOWER model is available in an open
skid version. Exhaust ships loose.
WINPOWER Sound-Pak: Specify
optional sound attenuated enclosure when
ordering.
Convenient Customer
Connections
All customer connection points are
centrally located to make AC and
DC connections quick and easy.
The DC control wires are connected
to a clearly labeled and convenient
terminal block. A terminal block is
installed for the factory wired multi-
stage battery charger and thermostat
controlled jacket heater.
Stamford Generator Ends
The premium Stamford generators are sized for 125
o
/40
o
C operation. Standard
features like 100% copper windings, automatic voltage regulators and <5% THD
make these generators suitable for almost any application. Single phase generators
use dedicated windings while all three phase voltages use 12 lead reconnectable
ends. Generators are available with optional EBS/PMG adders to increase motor
starting ability.
PSS 21kW-90kW
Powr-Pak
DR200D4 With Sound-Pak
and UL142 Sub-base Tank
Automatic Starting
Each generator with a sound attenuated housing comes with critical grade silencers
that reduce exhaust noise by 25-35 dba making these models suitable for use in
residential and commercial applications.
11